Space-Saving Integrated Architecture

Combined PCC with APFC Panels

Integrated Main Power Distribution with Automatic Power Factor Correction

The MOBY Combined Power Control Center (PCC) with Integrated APFC is a modern space-saving industrial electrical solution. By housing the main LT incomer air circuit breakers, multiple outgoing feeder breaker compartments, and a multi-step automatic capacitor bank within a single unified, factory-coupled cubicle assembly, it reduces substation civil room footprint by up to 40% and completely eliminates costly external power cable interconnections.

PCC Incomer Rating 800A to 4000A 4-Pole ACB
Integrated APFC Bank 150 kVAr to 800 kVAr
Busbar Fault Rating 50 kA / 65 kA for 1 Second
Enclosure Separation Form 3b / Form 4 Compartmentalized
✓ 100% Factory Routine Tested ✓ Custom Ratings Built-to-Order ✓ ISO 9001:2008 Certified

Comprehensive Technical Specifications

Detailed parameter ratings, insulation limits, standards compliance, and fabrication tolerances engineered for Combined PCC with APFC Panels.

Technical Parameter Engineering Specification Compliance Standard / Condition
🔷 Incomer & Power Distribution Section
Main Incomer Switchgear 4-Pole Air Circuit Breaker (ACB) Drawout Type with Microprocessor Trip Unit IS 13947-2 / IEC 60947-2
Incomer Current Ratings 800A / 1000A / 1250A / 1600A / 2000A / 2500A / 3200A / 4000A Standard Ratings
Rated Insulation / Impulse Voltage 1000 V AC / 8 kV Impulse (BIL) IEC 60947
Fault Withstand Capacity 50 kA / 65 kA rms for 1 Second (CPRI Tested) High Rupturing Capacity
Outgoing Feeder Options Air Circuit Breakers (ACB) or Molded Case Circuit Breakers (MCCB) Form 3b/4 Fully Compartmentalized
Busbar System Electrolytic Grade ETP Copper (99.9% IACS) or E91E Aluminium, insulated with heat-shrinkable PVC IS 5082 / IS 613
🔷 Integrated APFC Section
Capacitor Bank Rating 150 kVAr to 800 kVAr (Tailored to transformer kVA) Modular Steps
Capacitor Type Heavy-Duty Metallized Polypropylene (MPP) gas-filled self-healing cells 440V / 480V / 525V rated
Harmonic Reactors Copper / Aluminium wound 7% or 14% detuned series reactors Harmonic Blocking
Internal Busbar Coupling Solid copper/aluminium busbar bridge direct from main bus to APFC section No external cables needed
APFC Controller Intelligent DSP Microprocessor Controller with LCD screen & RS-485 Auto/Manual mode
Switching Protection Capacitor duty contactors with damping resistors & HRC fuse backups Zero transient surge
🔷 Mechanical & Enclosure Construction
Compartmentalization Form Form 3b / Form 4 (Separation between busbars, functional units, and cable alleys) IS 8623 / IEC 61439
Sheet Steel Gauge 2.0 mm CRCA frame, doors, and side covers / 2.5 mm gland plates Heavy-Duty Industrial
Surface Coating 7-Tank phosphating process with electrostatically applied pure polyester powder coat (80μm) RAL 7032 / 7035
Cable Entry Top or Bottom entry with removable 3mm non-magnetic brass/aluminium gland plates Flexible site cable termination
Degree of Ingress Protection IP42 (Standard ventilated) / IP54 (Filter fan pressurized) IS/IEC 60529

Key Engineering & Operational Features

Why electrical consultants, industrial plants, and utility engineers specify MOBY Combined PCC with APFC Panels.

🏢

Up to 40% Substation Footprint Reduction

Eliminates the need for a separate APFC room or freestanding capacitor panel, allowing compact electrical room design and major civil construction savings.

🔗

Pre-Engineered Internal Bus Coupling

APFC bank is directly bus-coupled to the primary PCC distribution busbars inside the factory, eliminating dozens of meters of expensive heavy-gauge interconnecting copper cables.

🛡️

Enhanced Personnel Safety (Form 3b/4)

Individual isolated sheet-steel compartments for incomer ACB, outgoing feeders, busbars, and capacitor steps prevent accidental contact with live buses during maintenance.

⚡

Immediate Reactive Power Compensation

Direct bus coupling ensures minimal impedance between the inductive main load and the capacitor bank, providing instant power factor correction and voltage stabilization.

⚙️

Single Factory Tested Assembly

The combined unit is manufactured, busbar-torqued, control-wired, and rigorously tested as a single integrated assembly before dispatch, ensuring flawless site commissioning.

📊

Centralized Digital Metering & SCADA

Front door features centralized multi-function digital power meters, APFC status controllers, breaker trip indicators, and Modbus RTU communication terminals.

Certified Quality & Factory Testing Standards

⚡ IS 8623 / IEC 61439 Form 3b/4

Every Combined PCC with APFC Panels is manufactured under strict ISO 9001:2008 quality control protocols and subjected to comprehensive routine testing at our Kolkata facility before dispatch.

✔ Full short-time withstand current testing up to 50kA/1s on primary busbars and dropper joints.
✔ Temperature rise test verifying busbar temperature limits under 100% continuous rated current load.
✔ High voltage power frequency dielectric test at 2.5 kV for 1 minute between phases and phase-to-ground.
✔ Insulation resistance testing before and after dielectric tests exceeding 100 MΩ.
✔ Complete sequential logic functional test of ACB trip releases, interlocking, and APFC auto-step switching.

Target Industrial Sectors & Deployment Scenarios

Engineered and tested for severe continuous operational duty across diverse sectors:

🏭 Heavy Manufacturing Plants 🏭 High-Rise Commercial Office Towers 🏭 Shopping Malls & Entertainment Multiplexes 🏭 Steel & Rolling Facilities 🏭 Pharmaceutical Formulations 🏭 Automobile Ancillary Hubs 🏭 Process Chemical Facilities

Related Switchgears & Equipment

Explore complementary electrical power distribution and protection units manufactured by Moby.

Frequently Asked Questions

Authoritative engineering answers regarding voltage ratings, CPRI testing, custom SLD fabrication, and warranty for Combined PCC with APFC Panels.

What are the technical voltage and breaking ratings for MOBY Combined PCC with APFC Panels? +

Primary Parameter Ratings: MOBY Combined PCC with APFC Panels is engineered for rated voltage 800A to 4000A 4-Pole ACB and rated normal current 150 kVAr to 800 kVAr. It is built to withstand prospective short-circuit breaking currents up to 40 kA for 3 seconds, fully adhering to national and international power engineering guidelines.

Is MOBY Combined PCC with APFC Panels CPRI tested and certified? +

Certification & Type Testing: Yes, MOBY Combined PCC with APFC Panels is IS 8623 / IEC 61439 Form 3b/4. All switchgears undergo comprehensive type-testing at the Central Power Research Institute (CPRI) and are routine tested (high-voltage dielectric withstand, contact resistance, and operational timing) at our ISO 9001:2008 certified Kolkata manufacturing facility prior to customer dispatch.

Can this equipment be customized according to our single-line diagram (SLD)? +

Custom Engineering Capabilities: Yes, Moby Electrotech specializes in custom-engineered electrical switchgear systems. Our Kolkata engineering team customizes incoming/outgoing feeder arrangements, CT/PT ratios, numerical protection relays, busbar ratings, enclosure dimensions, and ingress protection (IP42 to IP55) to match your exact site layout and SLD.

What is the standard warranty and quotation timeline for Combined PCC with APFC Panels? +

Commercial Terms & Warranty: All MOBY equipment carries an engineering equipment warranty of 12 months from commissioning or 18 months from delivery. Technical commercial quotations are typically provided within 24 to 48 hours following single-line diagram (SLD) review.

Request Technical Quote for Combined PCC with APFC Panels

Our senior electrical engineering team will review your single-line diagram (SLD), system voltage, and breaking requirements to provide a competitive quotation within 24 hours.

⚡ Direct Factory Response • Confidential Single-Line Diagram Reviews